“150”, Aptitude Test Questions and Answers for Engineer Grade ii - Electronical & Electronics – TANESCO.
ABSTRACT
This aptitude test preparation package
contains 150 multiple-choice questions and answers designed to prepare
candidates for the position of Engineer Grade II – Electrical and
Electronics at the Tanzania Electric Supply Company Limited (TANESCO). The
questions assess candidates’ theoretical knowledge and practical understanding
of electrical power systems, electrical machines, electronics, power generation
and transmission, protection systems, instrumentation, control systems,
industrial automation, electrical safety and technical calculations. They
feature challenging, closely related answer options designed to test technical
accuracy, critical thinking and problem-solving abilities. Each question is
accompanied by a correct answer and a detailed explanation to strengthen
understanding and improve candidates’ confidence and readiness for the aptitude
test.
Prepared for: Candidates applying for Engineer
Grade ii - Electronical & Electronics – TANESCO.
Independent aptitude-test preparation
resource; not an official TANESCO publication.
0628729934.
Date: November 20, 2026
Dear applicants,
This collection of 150 multiple-choice
questions and answers is designed to help candidates revise electrical trade
knowledge relevant to aptitude tests and recruitment assessments for Artisan
Grade II (Automobile) – TANESCO. It is an independent preparation resource, not
an official TANESCO examination paper, and it does not guarantee that any
question will appear in a recruitment assessment. I wish you success in your
preparation and recruitment process!
Warm regards,
Engineer Grade ii - Electronical &
Electronics – TANESCO. Aptitude Test Preparation Guide
Independent aptitude-test preparation
guide for candidates applying for Engineer Grade ii - Electronical &
Electronics – TANESCO. Not an official TANESCO publication.
Engineer Grade
ii - Electronical & Electronics – TANESCO.
150 Aptitude
Test Questions and Answers
Question 1
A three-phase
distribution feeder supplies a balanced load of 500 kW at a line voltage of 400
V and a power factor of 0.80 lagging. An engineer proposes installing a
capacitor bank to improve the power factor to 0.95 lagging. Assuming constant
active power, what is the approximate reactive power rating required for the
capacitor bank?
A. 125 kVAr
B. 180 kVAr
C. 211 kVAr
D. 220 kVAr
Correct
Answer: C. 211 kVAr
Rationale: Power factor correction reduces the
reactive power drawn from the supply while maintaining constant active power.
The initial reactive power is
\(Q_1=P\tan(\cos^{-1}0.80)=500\times0.75=375\text{ kVAr}\). At the improved
power factor of 0.95, the new reactive power is
\(Q_2=500\tan(\cos^{-1}0.95)\approx164.3\text{ kVAr}\). Therefore, the required
capacitor bank rating is \(Q_c=Q_1-Q_2=375-164.3=210.7\text{ kVAr}\),
approximately 211 kVAr. The capacitor bank supplies the difference between the
initial and desired reactive power, reducing the current drawn from the supply
and improving the system power factor.
Question 2
A 500 kVA, 11
kV/400 V distribution transformer has an impedance of 5% on its rated base.
Assuming an infinitely strong upstream supply and neglecting upstream
impedance, what is the approximate three-phase symmetrical short-circuit
current at the transformer's 400 V terminals?
A. 14.4 kA
B. 10.8 kA
C. 18.2 kA
D. 7.2 kA
Correct
Answer: A. 14.4 kA
Rationale: The rated secondary current is determined
using \(I_r=S/(\sqrt{3}V_L)\). Substituting the values gives
\(I_r=500,000/(\sqrt{3}\times400)=721.7\text{ A}\). Since the transformer
impedance is 5%, its per-unit impedance is 0.05. The approximate short-circuit
current is therefore \(I_{sc}=I_r/0.05=14,434\text{ A}\), or approximately 14.4
kA. Transformer impedance limits the fault current, and a lower percentage
impedance results in a higher prospective short-circuit current. This
calculation is fundamental when selecting circuit breakers, busbars and
protective equipment for distribution substations.
Question 3
A three-phase
induction motor operates from a 50 Hz supply and has six poles. Under a
particular mechanical load, its rotor speed is measured at 960 revolutions per
minute. What is the motor's percentage slip?
A. 2%
B. 6%
C. 8%
D. 4%
Correct
Answer: D. 4%
Rationale: The synchronous speed of an induction
motor is calculated using \(N_s=120f/P\), where \(f\) is the supply frequency
and \(P\) is the number of poles. Therefore, \(N_s=120\times50/6=1,000\text{
rpm}\). The percentage slip is calculated as \(s=(N_s-N_r)/N_s\times100\),
where \(N_r\) is the actual rotor speed. Substituting the values gives
\(s=(1,000-960)/1,000\times100=4\%\). Slip is necessary for torque production
because the rotor must rotate below synchronous speed to maintain relative
motion between the rotating magnetic field and the rotor conductors. An
induction motor operating at synchronous speed under normal motoring conditions
would not develop electromagnetic torque.
Question 4
An engineer is
designing a series RLC circuit for a frequency-selective electronic
application. The circuit contains an inductance of 50 mH and a capacitance of
20 μF. At approximately what frequency will the circuit experience series
resonance?
A. 100 Hz
B. 159 Hz
C. 225 Hz
D. 318 Hz
Correct
Answer: B. 159 Hz
Rationale: Series resonance occurs when the
inductive reactance equals the capacitive reactance, causing the net reactance
to become zero. The resonant frequency is determined by \(f_r=1/(2\pi\sqrt{LC})\).
Converting the component values gives \(L=0.05\text{ H}\) and
\(C=20\times10^{-6}\text{ F}\). Therefore,
\(f_r=1/[2\pi\sqrt{0.05\times20\times10^{-6}}]\approx159.15\text{ Hz}\). At
this frequency, the impedance of an ideal series RLC circuit is purely
resistive and reaches its minimum value, while the current reaches its maximum
value for a fixed applied voltage. This characteristic is important in
designing filters, tuned circuits and frequency-selective electronic systems.
Question 5
An operational
amplifier is configured as an inverting amplifier with an input resistance of
10 kΩ and a feedback resistance of 100 kΩ. If the input voltage is 0.25 V and
the amplifier operates within its linear region, what is the expected output
voltage?
A. −2.5 V
B. +2.5 V
C. −0.25 V
D. +25 V
Correct
Answer: A. −2.5 V
Rationale: The voltage gain of an ideal inverting
operational amplifier is \(A_v=-R_f/R_{in}\), where \(R_f\) is the feedback
resistance and \(R_{in}\) is the input resistance. The gain is therefore
\(-100/10=-10\). The output voltage is \(V_o=A_vV_{in}=-10\times0.25=-2.5\text{
V}\). The negative sign indicates that the output signal is inverted by 180
degrees relative to the input signal. The inverting configuration uses negative
feedback to maintain an approximately constant potential at the inverting
input, commonly referred to as a virtual ground when the non-inverting input is
grounded. This arrangement is widely used in signal conditioning, measurement
circuits and electronic control systems.
Question 6
A single-phase
full-wave bridge rectifier is supplied by a 50 Hz AC source. Assuming ideal
diodes and a resistive load, what is the fundamental frequency of the rectified
output ripple?
A. 25 Hz
B. 50 Hz
C. 100 Hz
D. 200 Hz
Correct
Answer: C. 100 Hz
Rationale: A full-wave bridge rectifier converts
both the positive and negative half-cycles of the AC input into output pulses
of the same polarity. Consequently, the output ripple frequency is twice the
input supply frequency. For a 50 Hz supply, the ripple frequency is
\(f_r=2f=2\times50=100\text{ Hz}\). This is different from a half-wave
rectifier, which produces a ripple frequency equal to the supply frequency. The
distinction is important when selecting smoothing capacitors and designing DC
power supplies because the ripple frequency directly affects the magnitude of
voltage fluctuations at the rectifier output. A suitable filter is normally
required to obtain a sufficiently stable DC voltage.
Question 7
During the design
of an electronic switching circuit for a power conversion application, an
engineer selects a power MOSFET instead of a conventional bipolar junction
transistor. Which characteristic most directly explains the MOSFET's
suitability for voltage-controlled switching applications?
A. It requires
continuous base current to maintain conduction and switching.
B. Its insulated
gate provides very high input resistance with negligible steady-state gate
current.
C. Its collector
current remains directly proportional to the base current during operation.
D. Its conduction
losses remain constant regardless of the load current.
Correct
Answer: B. Its insulated gate provides very high input resistance with
negligible steady-state gate current.
Rationale: A power MOSFET is a voltage-controlled
semiconductor device in which the gate-to-source voltage controls the formation
of a conducting channel. Its gate is electrically insulated from the
semiconductor channel by a dielectric layer, resulting in very high input
resistance and negligible steady-state gate current. However, current is
required to charge and discharge the gate capacitance during switching, making
an appropriate gate driver important. Unlike a bipolar junction transistor,
which requires base current to sustain conduction, a MOSFET is primarily
controlled by its gate voltage. This characteristic makes MOSFETs suitable for
high-frequency switching converters, electronic motor drives and power
management circuits.
Question 8
A technician is
inspecting a current transformer installed in a high-voltage substation. During
maintenance, the secondary circuit is accidentally disconnected while the
primary conductor remains energised and carries current. What is the most
significant electrical hazard created by this condition?
A. The primary
current immediately increases beyond its rated value
B. The secondary
voltage becomes zero because the magnetic circuit is interrupted
C. The
transformer automatically transfers the primary current into the equipment
earth
D. A dangerously
high voltage may develop across the open secondary terminals
Correct
Answer: D. A dangerously high voltage may develop across the open secondary
terminals
Rationale: A current transformer is designed to
operate with its secondary circuit connected to a low-impedance burden,
allowing the secondary current to oppose the magnetising effect of the primary
current. If the secondary is opened while the primary remains energised, the
opposing secondary ampere-turns disappear and the core flux can increase
substantially. This can induce a dangerously high voltage across the open
secondary terminals, creating risks of electric shock, insulation breakdown and
core overheating due to excessive flux and increased core losses. Current
transformer secondary circuits must therefore be short-circuited using
appropriate shorting terminals before disconnecting instruments or protective
relays. Unlike a voltage transformer, a current transformer must never be
operated with its secondary circuit open while primary current is flowing.
Question 9
A balanced
three-phase industrial load connected to a 400 V supply consumes 30 kW of
active power at a power factor of 0.80 lagging. What is the approximate line
current drawn by the load?
A. 43.3 A
B. 65.0 A
C. 54.1 A
D. 75.2 A
Correct
Answer: C. 54.1 A
Rationale: The active power consumed by a balanced
three-phase load is given by \(P=\sqrt{3}V_LI_L\cos\phi\). Rearranging the
expression gives \(I_L=P/(\sqrt{3}V_L\cos\phi)\). Substituting the given values
gives \(I_L=30,000/(\sqrt{3}\times400\times0.80)\approx54.13\text{ A}\). The
correct line current is therefore approximately 54.1 A. The power factor must
be included because only the component of apparent power associated with the
in-phase current contributes to active power consumption. This calculation is
important when determining feeder loading, selecting protective devices,
evaluating conductor capacity and assessing the operating conditions of
three-phase electrical installations.
Question 10
An electronic
measurement system is designed to acquire a sinusoidal signal with a frequency
of 5 kHz. The analogue-to-digital converter samples the signal at 8 kHz without
an appropriate anti-aliasing filter. What apparent frequency can be produced by
aliasing within the Nyquist frequency range?
A. 3 kHz
B. 4 kHz
C. 5 kHz
D. 8 kHz
Correct
Answer: A. 3 kHz
Rationale: The Nyquist frequency is half the
sampling frequency. For an 8 kHz sampling rate, the Nyquist frequency is 4 kHz.
Since the actual input signal is 5 kHz, it exceeds the Nyquist limit and cannot
be uniquely represented by the sampled data. The apparent aliased frequency is
calculated as \(|f_s-f_{in}|=|8-5|=3\text{ kHz}\). Thus, a 5 kHz signal can
appear as a 3 kHz signal in the sampled measurements. This phenomenon is called
aliasing and can lead to incorrect frequency measurements, distorted digital
representations and inaccurate monitoring of electrical signals. An analogue
anti-aliasing low-pass filter should be applied before sampling to attenuate
frequencies above the permissible input bandwidth.
Question 11
A synchronous
generator is required to produce electrical power at a frequency of 50 Hz. If
the generator has four magnetic poles, at what rotational speed must its rotor
operate under normal synchronous conditions?
A. 750 rpm
B. 1,500 rpm
C. 2,000 rpm
D. 3,000 rpm
Correct
Answer: B. 1,500 rpm
Rationale: The synchronous speed of an AC generator
is determined by the relationship \(N_s=120f/P\), where \(f\) is the generated
electrical frequency and \(P\) is the number of magnetic poles. Substituting 50
Hz and four poles gives \(N_s=(120\times50)/4=1,500\text{ rpm}\). Therefore,
the rotor must rotate at 1,500 rpm to produce an electrical frequency of 50 Hz.
Unlike an induction motor, a synchronous generator operates with its rotor
locked in synchronism with the rotating magnetic field. The relationship
between pole number and rotational speed is fundamental in power station
generator design because the required mechanical speed depends on the
electrical frequency and the number of poles selected.
Question 12
A DC-DC buck
converter operates under ideal continuous conduction conditions. Its input
voltage is 200 V, and its required output voltage is 80 V. What duty cycle
should the switching device have to maintain the required output voltage?
A. 20%
B. 60%
C. 80%
D. 40%
Correct
Answer: D. 40%
Rationale: An ideal buck converter reduces a DC
input voltage to a lower DC output voltage by controlling the switching duty
cycle. Under continuous conduction conditions and assuming ideal switching
components, the relationship is \(V_o=DV_{in}\), where \(D\) is the duty cycle.
Rearranging gives \(D=V_o/V_{in}=80/200=0.4\). Converting this to a percentage
gives 40%. The duty cycle represents the fraction of each switching period
during which the semiconductor switch remains in the ON state. In practical
converters, semiconductor voltage drops, switching losses and inductor
resistance may cause the actual duty cycle to differ slightly from the ideal
calculated value. Buck converters are widely used in DC power supplies, battery
systems and electronic equipment.
Question 13
An engineer
designs a resistive voltage divider consisting of a 10 kΩ upper resistor and a
5 kΩ lower resistor connected across a 12 V DC supply. A 5 kΩ measuring
instrument is subsequently connected across the lower resistor. Assuming ideal
resistors and negligible instrument input capacitance, what voltage will the
instrument measure?
A. 2.4 V
B. 3.0 V
C. 4.0 V
D. 6.0 V
Correct
Answer: A. 2.4 V
Rationale: Before the measuring instrument is
connected, the voltage across the 5 kΩ lower resistor is determined by the
voltage divider relationship, giving \(V_o=12\times5/(10+5)=4\text{ V}\).
However, connecting the measuring instrument introduces an additional 5 kΩ
resistance in parallel with the lower resistor. The effective lower resistance
becomes \(R_L=(5\times5)/(5+5)=2.5\text{ kΩ}\). The loaded output voltage is
therefore \(V_o=12\times2.5/(10+2.5)=2.4\text{ V}\). This reduction is known as
the loading effect. It occurs because the measuring instrument draws current
and changes the effective resistance of the divider. High-input-impedance
instruments are preferred when measuring voltage in sensitive electronic circuits
because they minimise loading errors.
Question 14
A distribution
feeder is protected by two overcurrent relays installed at different points
along the same radial circuit. During a downstream fault, the engineer wants
the relay nearest to the fault to operate first while the upstream relay
provides backup protection after a suitable delay. Which protection principle
is being applied?
A. Differential
protection based on current comparison
B. Distance
protection based on measured impedance
C. Time grading
for selective overcurrent protection
D. Directional
protection based on power flow angle
Correct
Answer: C. Time grading for selective overcurrent protection
Rationale: Time grading is a protection coordination
technique in which overcurrent relays are assigned operating times according to
their positions within a radial distribution network. The relay nearest to the
downstream fault is normally configured to operate first, isolating the
smallest possible section of the network. The upstream relay is assigned a
longer operating time so that it can provide backup protection if the
downstream relay or its associated circuit breaker fails. A suitable grading
margin must be maintained to accommodate relay operating tolerances,
circuit-breaker interruption time and other coordination requirements. This
approach improves supply continuity because a fault on one section does not
unnecessarily disconnect healthy upstream sections of the distribution network.
Differential, distance and directional protection use different operating
principles and are not equivalent to time grading.
Question 15
A pressure
transmitter uses a standard 4–20 mA current loop to represent a pressure range
of 0–100 bar. During operation, the receiving instrument measures a loop
current of 12 mA. What pressure does this current represent?
A. 40 bar
B. 50 bar
C. 60 bar
D. 75 bar
Correct
Answer: B. 50 bar
Rationale: In a standard 4–20 mA instrumentation
loop, 4 mA represents the lower measurement limit and 20 mA represents the
upper measurement limit. The measurement span is therefore 16 mA. A measured
current of 12 mA is 8 mA above the lower limit, representing \(8/16=0.5\), or
50% of the measurement range. Since the pressure range is 0–100 bar, the
corresponding pressure is \(0.5\times100=50\text{ bar}\). The general
conversion equation is \(P=P_{\min}+\frac{I-4}{16}(P_{\max}-P_{\min})\). The 4
mA live-zero arrangement also allows the receiving system to distinguish a
valid zero measurement from certain fault conditions, such as an open-circuit
loop.
Question 16
A programmable
logic controller (PLC) is controlling an automated pumping system. During
normal operation, the controller reads input signals, executes its programmed
logic and updates the output devices. Which sequence most accurately represents
the conventional PLC scan cycle?
A. Execute
program logic, update outputs, then read inputs
B. Update
outputs, read inputs, then execute program logic
C. Read inputs,
update outputs, then execute program logic
D. Read inputs,
execute program logic, then update outputs
Correct
Answer: D. Read inputs, execute program logic, then update outputs
Rationale: In a conventional PLC scan cycle, the
controller first reads the states of its physical input terminals and stores
the values in an input image or process image. It then executes the user
program using the stored input values and evaluates the required control
decisions. After program execution, the PLC updates its output image and
transfers the resulting output states to the physical output devices, such as
contactors, indicator lamps and control valves. The cycle then repeats
continuously while the controller is operating. This sequence is important
because the program generally processes a snapshot of the inputs taken at the
beginning of the scan rather than continuously reading every input during every
instruction. Understanding scan behaviour is essential when diagnosing response
delays, interlocking problems and time-sensitive control applications.
Question 17
Two three-phase
power transformers are to be operated in parallel to supply a common
distribution busbar. Both transformers have the same rated voltage and power
capacity. Which combination of electrical characteristics must be suitably
matched to ensure satisfactory parallel operation and appropriate load sharing?
A. Voltage
ratios, phase sequence, polarity, vector groups and percentage impedances.
B. Core
materials, cooling arrangements, insulation classes and tank dimensions.
C. Primary
conductor lengths, winding temperatures, core weights and rated currents.
D. Total iron
losses, oil volumes, winding dimensions and cooling fan capacities.
Correct
Answer: A. Voltage ratios, phase sequence, polarity, vector groups and
percentage impedances.
Rationale: Successful parallel operation of
three-phase transformers requires compatibility of their electrical
characteristics. Their voltage ratios must be sufficiently equal to minimise
circulating currents caused by differences in secondary induced voltages. They
must also have the correct polarity, phase sequence and compatible vector
groups to ensure that their secondary voltages have the appropriate phase
relationships. Their percentage impedances and impedance angles should be
suitably matched to achieve appropriate load sharing and prevent one
transformer from becoming excessively loaded. Even transformers with identical
rated capacities may share loads unequally if their impedances differ
significantly. Cooling arrangements and physical construction do not independently
determine electrical compatibility for parallel operation.
Question 18
An electronic
low-pass RC filter consists of a 3.3 kΩ resistor and a 10 nF capacitor.
Assuming an ideal first-order filter, what is its approximate cut-off
frequency?
A. 1.59 kHz
B. 3.30 kHz
C. 4.82 kHz
D. 9.65 kHz
Correct
Answer: C. 4.82 kHz
Rationale: The cut-off frequency of a first-order RC
low-pass filter is determined by \(f_c=1/(2\pi RC)\). The resistance is
\(3,300\ \Omega\), while the capacitance is \(10\times10^{-9}\text{ F}\). Their
product is \(RC=33\times10^{-6}\text{ s}\). Therefore,
\(f_c=1/[2\pi(33\times10^{-6})]\approx4,822\text{ Hz}\), or approximately 4.82
kHz. At the cut-off frequency, the magnitude of the output voltage is
approximately 70.7% of its passband value, corresponding to a reduction of
approximately 3 dB. Frequencies significantly above the cut-off frequency are
progressively attenuated, making this type of filter useful for reducing
high-frequency noise and limiting the bandwidth of analogue measurement
circuits.
Question 19
A transmission
line supplies a constant three-phase active power to a load at a constant power
factor. An engineer proposes doubling the transmission voltage while
maintaining the same power delivery and conductor resistance. Assuming balanced
operation and negligible changes in power factor, how will the resistive power
losses in the conductors change?
A. They will
increase by 100%
B. They will
decrease to one-quarter of their original value
C. They will
decrease to one-half of their original value
D. They will
remain approximately unchanged
Correct
Answer: B. They will decrease to one-quarter of their original value
Rationale: For a balanced three-phase system, active
power is given by \(P=\sqrt{3}V_LI_L\cos\phi\). If the transmitted active power
and power factor remain constant, doubling the line voltage reduces the line
current to one-half of its original value. Resistive power losses are
determined by \(P_{\text{loss}}=3I_L^2R\), assuming equal phase conductor
resistance. Substituting half the original current gives
\(P_{\text{loss,new}}=3(0.5I_L)^2R=0.25P_{\text{loss,old}}\). Therefore, the
losses decrease to one-quarter of their original value, representing a 75%
reduction. This is one of the principal reasons why electrical power is
transmitted at high voltages: higher transmission voltage reduces current for a
given power transfer and consequently reduces conductor heating and resistive
energy losses.
Question 20
A substation
engineer is assessing the effect of neutral earthing impedance on a
single-line-to-ground fault in a three-phase power system. Which statement best
describes the principal function of inserting an impedance between the
transformer neutral and earth?
A. It increases
the normal phase-to-phase operating voltage
B. It eliminates
the need for earth fault protection equipment
C. It prevents
all fault current from flowing through the transformer windings
D. It limits the
magnitude of earth fault current to a designed level
Correct
Answer: D. It limits the magnitude of earth fault current to a designed level
Rationale: Neutral earthing impedance is introduced
between the neutral point of a power transformer or generator and earth to
control the magnitude of current flowing during an earth fault. Depending on
the system design, the impedance may be resistive or reactive. By limiting the
fault current, it can reduce thermal and mechanical stresses on equipment,
minimise damage at the fault location and influence the operation and
sensitivity of earth fault protection systems. The selected impedance must
still permit sufficient fault current for the protection scheme to detect and
isolate the fault reliably. Neutral earthing does not eliminate the need for
protective relays, nor does it prevent all current from flowing through
transformer windings. Its value and configuration must be coordinated with the
network's insulation, protection and grounding requirements.
Question 21
An engineer is
comparing two full-wave rectifier configurations: a centre-tapped rectifier and
a four-diode bridge rectifier. If both are supplied by equivalent secondary
voltage arrangements, what is the approximate peak inverse voltage (PIV)
experienced by each diode in a conventional ideal bridge rectifier?
A. Equal to the
peak secondary voltage
B. Twice the peak
secondary voltage
C. Half the peak
secondary voltage
D. Four times the
peak secondary voltage
Correct
Answer: A. Equal to the peak secondary voltage
Rationale: In a conventional single-phase full-wave
bridge rectifier, two diodes conduct during each half-cycle while the other two
remain reverse-biased. The maximum reverse voltage experienced by an individual
non-conducting diode is approximately equal to the peak voltage of the
transformer secondary winding supplying the bridge. Therefore, the PIV rating
required for each diode is approximately \(V_m\), where \(V_m\) is the peak
secondary voltage. This differs from a centre-tapped full-wave rectifier, where
each non-conducting diode may experience a PIV of approximately \(2V_m\), with
\(V_m\) defined as the peak voltage across one half of the secondary winding.
Correct PIV selection is important because exceeding the reverse-voltage rating
can cause diode breakdown and permanent damage.
Question 22
An engineer is
assessing the stability of a feedback control system using a frequency-response
plot. At the frequency where the open-loop gain magnitude crosses unity (0 dB),
the measured phase angle is −140°. What is the approximate phase margin of the system?
A. 20°
B. 30°
C. 40°
D. 50°
Correct
Answer: C. 40°
Rationale: Phase margin is a measure of the relative
stability of a feedback control system and is determined at the gain crossover
frequency, where the open-loop gain magnitude is unity or 0 dB. It is
calculated as \(PM=180^\circ+\phi\), where \(\phi\) is the phase angle at the
gain crossover frequency for the conventional negative-feedback stability
assessment. Substituting the measured phase angle gives
\(PM=180^\circ-140^\circ=40^\circ\). A positive phase margin indicates a degree
of stability under the assumed system conditions, while a very small phase
margin generally suggests a tendency towards oscillatory behaviour and poor
damping. A larger phase margin generally indicates greater relative stability,
although the desired value depends on system response requirements, bandwidth
and performance specifications.
Question 23
A three-phase
distribution feeder supplies an industrial load located several kilometres from
a substation. During peak demand, the voltage measured at the receiving end
falls below the permissible operating range. The conductor material and
operating current are unchanged. Which modification would most directly reduce
the resistive component of the feeder's voltage drop?
A. Increasing the
operating frequency while retaining the same conductor dimensions
B. Increasing the
cross-sectional area of the feeder conductors
C. Reducing the
insulation thickness while retaining the same conductor material
D. Increasing the
number of connected loads along the feeder
Correct
Answer: B. Increasing the cross-sectional area of the feeder conductors
Rationale: The resistance of a conductor is given by
\(R=\rho L/A\), where \(\rho\) is the resistivity of the conductor material,
\(L\) is its length and \(A\) is its cross-sectional area. Increasing the
cross-sectional area reduces conductor resistance because the resistance is
inversely proportional to the area. Since the resistive component of voltage
drop depends on current and conductor resistance, reducing resistance directly
reduces this component of voltage drop under the same operating current. The
increase in conductor size can also reduce resistive heating and improve
current-carrying capacity. Other factors, including conductor reactance, power
factor, operating temperature and feeder configuration, must also be considered
when carrying out a complete voltage-drop assessment.
Question 24
During the
testing of an electronic control circuit, an engineer uses an oscilloscope with
a probe set to ×10 attenuation. However, the oscilloscope channel is configured
for a ×1 probe. If the actual signal voltage at the probe tip is 50 V, what
voltage will the oscilloscope display?
A. 5 V
B. 10 V
C. 25 V
D. 50 V
Correct
Answer: A. 5 V
Rationale: A ×10 oscilloscope probe attenuates the
input signal by a factor of ten before it reaches the oscilloscope input. When
the oscilloscope channel is configured for ×1, it assumes that the probe does
not attenuate the signal and therefore displays the reduced voltage received at
its input. For a 50 V signal at the probe tip, the oscilloscope receives
approximately \(50/10=5\text{ V}\) and displays 5 V. If the channel were
correctly configured for ×10, the oscilloscope would compensate for the probe
attenuation and display the actual 50 V signal. A mismatch between probe
attenuation and channel settings produces systematic measurement errors during
electronic equipment testing and fault diagnosis.
Question 25
During a routine
transformer test, engineers perform a short-circuit test by applying a reduced
voltage to one winding while the other winding is short-circuited. When rated
current is established, what does the measured input power primarily represent?
A. Core iron
losses.
B. Winding copper
losses.
C. Dielectric
insulation losses.
D. Mechanical
friction losses.
Correct
Answer: B. Winding copper losses.
Rationale: During a transformer short-circuit test,
a reduced voltage is applied to one winding while the other winding is
short-circuited. The applied voltage is adjusted until rated current flows
through the windings. Because the applied voltage is relatively low, the
magnetic flux and resulting core losses are small. Consequently, the measured
input power primarily represents the winding copper losses at the test current,
together with relatively small additional losses. This test is used to
determine equivalent series impedance and assess transformer load losses.
Question 26
A power
transformer is protected by a percentage differential protection scheme. During
energisation, the differential relay detects a substantial differential current
even though no internal fault exists. Which feature of modern transformer
differential relays is primarily intended to prevent unnecessary tripping under
this condition?
A.
Second-harmonic restraint to distinguish magnetising inrush current from
internal fault current.
B. Fifth-harmonic
restraint to distinguish normal transformer loading from external short
circuits.
C. Percentage
bias restraint to distinguish transformer energisation from normal load
current.
D. Zero-sequence
current elimination to prevent operation during transformer overexcitation.
Correct
Answer: A. Second-harmonic restraint to distinguish magnetising inrush current
from internal fault current.
Rationale: Transformer energisation produces
magnetising inrush current because the magnetic core may enter saturation
depending on the switching instant, residual flux and transformer
characteristics. This current can be considerably higher than the normal
magnetising current and may appear as differential current because it enters
the transformer without an equivalent current emerging from the secondary
terminals. Magnetising inrush current typically contains a significant
second-harmonic component, which modern differential relays use to identify the
energisation condition and restrain unnecessary tripping. Fifth-harmonic
restraint is commonly associated with overexcitation detection, while
percentage bias improves stability during external faults and current transformer
errors. Second-harmonic restraint therefore improves protection security
without unnecessarily compromising sensitivity to genuine internal faults.
Question 27
A three-phase
generator is represented by a balanced per-unit system with a prefault phase
voltage of 1.0 pu. Its positive-, negative- and zero-sequence impedances are
each equal to \(j0.2\) pu. A solid single-line-to-ground fault occurs at its
terminals. Neglecting fault resistance, what is the approximate magnitude of
the fault current in per unit?
A. 1.67 pu
B. 3.33 pu
C. 5.00 pu
D. 6.67 pu
Correct
Answer: C. 5.00 pu
Rationale: A single-line-to-ground fault requires
the positive-, negative- and zero-sequence networks to be connected in series
because the three sequence currents are equal during this type of fault. The
fault current is therefore calculated using \(I_f=3V/(Z_1+Z_2+Z_0+3Z_f)\),
where \(V\) is the prefault phase voltage and \(Z_f\) is the fault impedance.
Since the fault is solid, \(Z_f=0\). Substituting the given values gives
\(I_f=3(1.0)/(j0.2+j0.2+j0.2)=3/(j0.6)=-j5.0\text{ pu}\). The magnitude is
therefore 5.0 pu. This method is important in power system fault analysis
because the magnitude of a single-line-to-ground fault depends on all three
sequence impedances, unlike a balanced three-phase fault, which is primarily
determined by the positive-sequence network.
Question 28
A synchronous
generator is connected to a large interconnected power grid operating at a
constant frequency. The generator's mechanical input power remains unchanged,
but its field excitation is increased. Assuming the generator remains
synchronised with the grid, what is the most likely immediate operating effect?
A. Its rotational
speed increases independently of the grid frequency
B. Its active
power output increases while its reactive power remains constant
C. Its terminal
frequency increases while its mechanical input remains unchanged
D. Its reactive
power output generally increases while its active power remains approximately
unchanged
Correct
Answer: D. Its reactive power output generally increases while its active power
remains approximately unchanged
Rationale: When a synchronous generator is connected
to a strong interconnected grid, its rotational speed and electrical frequency
are constrained by the grid frequency. Its active power output is primarily
controlled by the mechanical power supplied by the prime mover, while its
reactive power exchange is strongly influenced by field excitation. Increasing
excitation raises the internal generated electromotive force relative to the
grid voltage and generally causes an overexcited generator to supply more
reactive power to the system. The generator does not independently increase its
speed or system frequency because it remains synchronised with the
interconnected network. This separation between active power control through
mechanical input and reactive power control through excitation is fundamental
to power station operation, voltage regulation and generator stability.
Question 29
A three-phase
induction motor is supplied through a variable frequency drive (VFD). The motor
is rated at 400 V and 50 Hz. An engineer reduces the supply frequency to 25 Hz
to operate the motor at approximately half its rated synchronous speed while
maintaining approximately constant air-gap flux. What fundamental voltage
should the VFD supply, assuming ideal constant voltage-to-frequency control?
A. 400 V
B. 200 V
C. 100 V
D. 300 V
Correct
Answer: B. 200 V
Rationale: The magnetic flux in an induction motor
is approximately proportional to the ratio of applied voltage to supply
frequency, provided that the stator resistance voltage drop is sufficiently
small. To maintain approximately constant air-gap flux, the voltage-to-frequency
ratio must remain constant. The rated ratio is \(400/50=8\text{ V/Hz}\). At 25
Hz, the required voltage is therefore \(V=8\times25=200\text{ V}\). Reducing
both voltage and frequency proportionally allows the motor to operate at a
lower speed without significantly weakening its magnetic field. If the
frequency were reduced without a corresponding reduction in voltage, excessive
magnetic flux could result, potentially causing magnetic saturation and
increased magnetising current. At very low frequencies, voltage boost may be
necessary to compensate for stator resistance effects.
Question 30
A three-phase
underground distribution cable has a manufacturer's reference current-carrying
capacity of 300 A under specified installation conditions. The actual
installation requires correction factors of 0.94 for ambient temperature, 0.80
for grouping and 0.90 for soil thermal conditions. What is the approximate
corrected current-carrying capacity?
A. 203 A
B. 225 A
C. 240 A
D. 254 A
Correct
Answer: A. 203 A
Rationale: Cable current-carrying capacity must be
adjusted when actual installation conditions differ from the reference
conditions used by the manufacturer. The corrected capacity is obtained by
multiplying the reference capacity by all applicable correction factors.
Therefore, \(I_z=300\times0.94\times0.80\times0.90=203.04\text{ A}\). The
corrected capacity is approximately 203 A. The ambient temperature factor
accounts for the effect of the surrounding temperature on the cable's ability
to dissipate heat, while the grouping factor accounts for mutual heating
between adjacent loaded cables. The soil thermal factor reflects the influence
of the surrounding soil's thermal characteristics on heat dissipation. Using
the uncorrected 300 A rating could result in excessive conductor temperature,
accelerated insulation deterioration and possible cable failure.
📘 Get the Full Aptitude Test Questions PDF through your Gmail (Questions 1–150)
You’ve just accessed the first 30 questions. The full set of 150 expertly prepared aptitude test questions for Engineer Grade ii - Electronical & Electronics – TANESCO, Is available, pay, and get access.
To get access to the full PDF, please make a payment of Tsh 10,000 to the LIPA numbers below:
After payment, please send a text message to notify us of your payment:
⚠️ Important Notice
- The PDF will be watermarked with your name and phone number and protected for personal use only.
- Redistribution, sharing, screenshotting, or copying the contents is strictly prohibited. When you share unlawfully, your name and phone number are visible and easy to trace as you leaked a document to other third parties.
- Legal action may be taken against the misuse of this material.
Thank you for supporting quality content. Best of luck in your interview preparation!