“150”, Aptitude Test Questions and Answers for Technician Grade II (Electrical/Electronics) – TANESCO.
ABSTRACT
This preparation package contains 150 structured
multiple-choice questions and answers designed to help candidates prepare for
the Technician Grade II – Electrical/Electronics (TANESCO) aptitude test in
Tanzania. The questions assess essential knowledge and practical understanding
of electrical and electronic engineering, including power generation and
distribution, electrical installations, transformers, motors, circuit
protection, fault diagnosis, testing instruments, industrial automation,
instrumentation and maintenance. They incorporate technical calculations,
practical scenarios and closely related answer options to challenge candidates'
analytical thinking, technical accuracy and problem-solving abilities. Each
question is accompanied by a correct answer and an explanatory rationale to
support effective learning, revision and examination preparation.
Prepared for: Candidates applying for Technician
Grade II (Electrical/Electronics) – TANESCO
Independent aptitude-test preparation
resource; not an official TANESCO publication.
0628729934.
Date: November 10, 2026
Dear applicants,
This collection of 150 multiple-choice
questions and answers is designed to help candidates revise electrical trade
knowledge relevant to aptitude tests and recruitment assessments for Technician
Grade II (Electrical/Electronics) – TANESCO. It is an independent preparation
resource, not an official TANESCO examination paper, and it does not guarantee
that any question will appear in a recruitment assessment. I wish you success
in your preparation and recruitment process!
Warm regards,
Technician Grade II (Electrical/Electronics) – TANESCO Aptitude Test Preparation Guide
Independent aptitude-test preparation
guide for candidates applying for Technician Grade II (Electrical/Electronics)
– TANESCO. Not an official TANESCO publication.
Technician Grade II (Electrical/Electronics)
– TANESCO.
150 Aptitude
Test Questions and Answers
Question 1. A
three-phase electrical motor operates from a 400 V supply and draws a line
current of 32 A at a power factor of 0.8 lagging. Assuming the motor operates
under balanced conditions, what is the approximate active electrical input
power?
A. 14.2 kW.
B. 16.8 kW.
C. 17.7 kW.
D. 22.2 kW.
Correct Answer:
C. 17.7 kW.
Rationale: The
active power consumed by a balanced three-phase load is calculated using
\(P=\sqrt{3}V_LI_L\cos\phi\), where \(V_L\) represents line voltage, \(I_L\) represents
line current and \(\cos\phi\) represents power factor. Substituting the given
values gives \(P=1.732\times400\times32\times0.8=17,736.96\) watts, equivalent
to approximately 17.7 kW. It is important to distinguish active power from
apparent power, which would be approximately 22.2 kVA in this case. Multiplying
voltage and current without considering the three-phase factor or power factor
would produce an incorrect result. This calculation is particularly relevant
when evaluating motor loading and electrical power consumption in industrial
installations.
Question 2. A
single-phase transformer has 660 turns in its primary winding and is supplied
with 11,000 V. If the transformer is required to produce an ideal secondary
voltage of 415 V, approximately how many turns should the secondary winding
contain?
A. 25 turns.
B. 40 turns.
C. 55 turns.
D. 75 turns.
Correct Answer:
A. 25 turns.
Rationale: The
transformer voltage ratio is directly proportional to the ratio of the number
of turns in the primary and secondary windings. The relationship is expressed
as \(V_p/V_s=N_p/N_s\). Rearranging gives \(N_s=N_p(V_s/V_p)\). Therefore,
\(N_s=660\times415/11000=24.9\), which is approximately 25 turns. A transformer
designed to reduce voltage from 11 kV to 415 V is a step-down transformer
because the secondary winding has considerably fewer turns than the primary
winding. The calculation assumes an ideal transformer, meaning winding
resistance, leakage reactance and other voltage losses are neglected.
Understanding the relationship between voltage and winding turns is essential
when assessing transformer specifications, winding arrangements and
transformation ratios.
Question 3. A
current transformer has a rated primary-to-secondary current ratio of 400/5 A.
During an electrical installation test, the primary conductor carries a current
of 240 A. What current should ideally be measured on the secondary side of the
current transformer?
A. 2.0 A.
B. 2.4 A.
C. 4.0 A.
D. 3.0 A.
Correct Answer:
D. 3.0 A.
Rationale: A
current transformer reduces a high primary current to a proportionally smaller
secondary current for measurement and protection purposes. Its transformation
ratio is determined by dividing the rated primary current by the rated
secondary current. In this case, the ratio is \(400/5=80\). Therefore, when the
primary current is 240 A, the secondary current is \(240/80=3\) A. This is an
ideal calculation that neglects the effects of excitation current and
measurement errors. A particularly important practical consideration is that
the secondary winding of an energized conventional current transformer must
never be left open-circuited because a dangerously high voltage may develop
across its terminals. Appropriate shorting arrangements must be used before
disconnecting secondary instruments or protection circuits.
Question 4. A
three-phase induction motor is designed to operate normally with its stator
windings connected in delta. When the same motor is started using a star-delta
starter, what happens to its starting line current compared with direct-on-line
starting in delta, assuming the same supply voltage and negligible supply
impedance?
A. It becomes
approximately one-half of the original current.
B. It becomes approximately one-third of the original current.
C. It becomes approximately two-thirds of the original current.
D. It remains approximately equal to the original current.
Correct Answer:
B. It becomes approximately one-third of the original current.
Rationale: In a
star-delta starting arrangement, the motor windings are initially connected in
star, meaning each winding receives a phase voltage equal to the line voltage
divided by \(\sqrt{3}\). Since the impedance of each winding is assumed
constant, the starting phase current is also reduced to approximately
\(1/\sqrt{3}\) of its delta-connected value. In delta, line current is
\(\sqrt{3}\) times phase current, whereas in star, line current equals phase
current. Combining these relationships shows that the star-connected starting
line current is approximately one-third of the direct-on-line delta starting
line current. The starting torque also falls to approximately one-third because
induction motor starting torque is approximately proportional to the square of
the applied voltage. This distinction is important when selecting motor
starting methods to reduce starting current and mechanical stress on electrical
installations.
Question 5. A
series RLC circuit is connected to a 50 Hz AC supply. If its inductance is 0.2
H, what capacitance will produce series resonance at the supply frequency?
A. 50.7 µF.
B. 63.7 µF.
C. 75.2 µF.
D. 100.5 µF.
Correct Answer:
A. 50.7 µF.
Rationale: Series
resonance occurs when the inductive reactance equals the capacitive reactance,
resulting in zero net reactance and a purely resistive circuit under ideal
conditions. The resonant frequency is given by \(f_r=1/(2\pi\sqrt{LC})\).
Rearranging the formula gives \(C=1/(4\pi^2f_r^2L)\). Substituting \(f_r=50\)
Hz and \(L=0.2\) H produces \(C=1/(4\pi^2\times50^2\times0.2)\), giving
approximately \(50.66\times10^{-6}\) farads or 50.7 µF. At resonance, the
inductive and capacitive reactances cancel each other, resulting in minimum
circuit impedance and maximum current for a fixed applied voltage. This
principle is important in electrical filtering, tuning circuits and
power-system applications involving reactive components.
Question 6. A
three-phase distribution circuit operates at 400 V and supplies a balanced load
drawing 25 A at a power factor of 0.8 lagging. The resistance of each conductor
is 0.18 Ω over the circuit length, while conductor reactance is negligible.
What is the approximate voltage drop across the three-phase circuit?
A. 3.60 V.
B. 4.50 V.
C. 6.24 V.
D. 7.79 V.
Correct Answer:
C. 6.24 V.
Rationale: For a
balanced three-phase circuit with negligible conductor reactance, the
approximate line-to-line voltage drop is calculated using \(\Delta
V=\sqrt{3}I_LR\cos\phi\), where \(R\) is the resistance of one conductor over
the complete circuit length. Substituting the given values gives \(\Delta
V=1.732\times25\times0.18\times0.8=6.235\) V, which is approximately 6.24 V.
This represents a voltage drop of about 1.56% of the 400 V supply. The power
factor must be included because only the resistance-related component of the
voltage drop is being considered. In actual electrical installations, conductor
reactance, temperature-dependent resistance, installation conditions and
applicable voltage-drop limits must also be considered when selecting conductor
sizes. This calculation is particularly relevant to distribution networks and
electrical installation design.
Question 7. A
power transformer receives an electrical input of 50 kW while its total iron
losses and copper losses under the existing operating condition are 0.8 kW and
1.2 kW respectively. What is the approximate operating efficiency of the
transformer?
A. 92%.
B. 94%.
C. 95%.
D. 96%.
Correct Answer:
D. 96%.
Rationale:
Transformer efficiency is the ratio of useful output power to input power,
expressed as a percentage. The total losses are obtained by adding iron losses
and copper losses, giving \(0.8+1.2=2\) kW. The output power is therefore
\(50-2=48\) kW. Applying the efficiency formula gives
\(\eta=(48/50)\times100=96\%\). Iron losses mainly arise from hysteresis and
eddy currents in the transformer core and are approximately constant at a fixed
voltage and frequency, whereas copper losses are caused by winding resistance
and vary approximately with the square of the load current. Understanding these
losses helps technicians assess transformer performance, investigate abnormal
heating and identify operating conditions that may reduce energy efficiency.
Question 8. An
electrical technician is selecting a circuit breaker for an installation where
the prospective short-circuit current at the point of installation has already
been established. Which characteristic of the circuit breaker must be adequate
to ensure that it can safely interrupt the maximum prospective fault current?
A. Rated
short-time withstand current.
B. Rated breaking capacity.
C. Rated making capacity.
D. Rated continuous current.
Correct Answer:
B. Rated breaking capacity.
Rationale: The
breaking capacity of a circuit breaker represents its ability to safely
interrupt a specified fault current under defined test conditions without
suffering unacceptable damage or creating an unsafe condition. When selecting a
circuit breaker, its rated breaking capacity must be equal to or greater than
the prospective short-circuit current at the installation point, with the
applicable rating and standard taken into account. Rated continuous current
serves a different purpose because it indicates the current the breaker is
designed to carry under specified conditions during normal operation. Rated
operational voltage concerns the voltage at which the device is intended to
operate, while rated insulation voltage relates to its insulation
characteristics. A breaker may have an adequate continuous current rating but
still be unsuitable if its breaking capacity is insufficient for the available
fault current.
Question 9. A
power transformer is protected by a differential protection system. During an
internal winding fault, the currents measured by the current transformers
installed on the primary and secondary sides become unequal after the
protection system has compensated for their respective ratios and phase
displacement. What is the most appropriate interpretation of this condition?
A. The
transformer may have developed an internal fault within its protected zone.
B. The transformer is experiencing a normal increase in magnetising current.
C. The transformer secondary load has developed a balanced operating condition.
D. The transformer is experiencing an external fault outside its protected
zone.
Correct Answer:
A. The transformer may have developed an internal fault within its protected
zone.
Rationale: Transformer
differential protection operates on the principle of comparing currents
entering and leaving a defined protection zone. Under normal operating
conditions and during external faults, properly compensated current
measurements should approximately balance, meaning the differential current
remains below the protection operating threshold. However, an internal fault
such as a winding-to-winding fault or winding-to-earth fault can produce a
significant difference between the compensated currents, causing the
differential relay to issue a trip command. The system must account for
transformer ratio differences, phase displacement, CT characteristics and
possible transient effects to avoid unwanted operation. A genuine differential
fault condition is therefore an indication requiring investigation rather than
an ordinary change in transformer loading. This protection arrangement is
particularly important for major transformers in transmission and distribution
substations.
Question 10. An
earth-leakage protection device is installed in a single-phase electrical
circuit supplying an industrial appliance. During operation, the current
flowing through the live conductor is greater than the current returning
through the neutral conductor. Which principle explains how the device detects
the abnormal condition?
A. It detects an
increase in current above the circuit's rated overload setting.
B. It detects a reduction in insulation resistance between live conductors.
C. It detects an imbalance between the outgoing and returning currents.
D. It detects an increase in current flowing through the protective conductor.
Correct Answer:
C. It detects an imbalance between the outgoing and returning currents.
Rationale: A
residual current device (RCD) detects leakage by comparing the current flowing
through the live conductor with the current returning through the neutral
conductor. Under normal operating conditions, these currents should be equal in
magnitude and opposite in direction. If part of the current escapes through an
unintended path, such as an earth conductor or a person in contact with an
exposed conductive part, the returning current becomes smaller than the
outgoing current. This difference creates a residual current that can cause the
RCD to disconnect the circuit when its operating threshold and time
requirements are reached. An RCD is primarily intended to provide protection
against residual-current faults and is not automatically a substitute for
overcurrent protection. Understanding this distinction is essential when
selecting and testing protective devices in electrical installations.
Question 11.
During scheduled maintenance of a low-voltage electrical installation, a
technician is required to determine whether the insulation between the live
conductors and earth has deteriorated. Which testing instrument is most
appropriate for this particular assessment?
A. Earth fault
loop impedance tester.
B. Continuity resistance tester.
C. Residual current device tester.
D. Insulation resistance tester.
Correct Answer:
D. Insulation resistance tester.
Rationale: An
insulation resistance tester, commonly known as a megohmmeter, is designed to
measure the resistance of electrical insulation by applying a specified DC test
voltage and measuring the resulting leakage current. It is particularly useful
when assessing insulation between conductors, between live conductors and
earth, and across appropriate electrical equipment insulation systems. A low
insulation resistance reading may indicate moisture ingress, contamination,
physical insulation damage or deterioration caused by ageing and thermal
stress. The installation must be safely isolated, verified dead and
appropriately prepared before testing, with sensitive electronic equipment
disconnected where necessary to prevent damage. A clamp meter measures current,
a frequency meter measures supply frequency, and a phase-sequence meter
identifies phase rotation; none of these instruments is intended to provide a
direct insulation resistance assessment.
Question 12. An
oscilloscope is connected to an electrical signal through a probe configured
with a 10:1 attenuation ratio. The oscilloscope displays a peak voltage of 2.4
V, and the probe attenuation factor has not been compensated for in the
oscilloscope settings. What is the actual peak voltage of the measured signal?
A. 0.24 V.
B. 24 V.
C. 12 V.
D. 240 V.
Correct Answer:
B. 24 V.
Rationale: A 10:1
oscilloscope probe reduces the voltage reaching the oscilloscope input to
one-tenth of the actual signal voltage. Therefore, when the displayed peak
voltage is 2.4 V and the instrument has not automatically compensated for the
probe attenuation, the actual signal voltage is obtained by multiplying the
displayed value by ten. Thus, \(V_{\text{actual}}=2.4\times10=24\) V. This
distinction is important because oscilloscope probes are designed to allow
measurements of higher voltages while reducing loading effects on the circuit
being tested. The technician must ensure that the probe attenuation setting and
oscilloscope channel configuration correspond correctly; otherwise, the
measured voltage may be interpreted incorrectly. The probe's voltage rating,
frequency response and grounding arrangements must also be considered before
taking measurements.
Question 13. A
single-phase full-wave bridge rectifier is supplied from a 50 Hz AC source.
Assuming ideal diodes and a continuous periodic input waveform, what is the
frequency of the principal rectified output ripple?
A. 25 Hz.
B. 50 Hz.
C. 100 Hz.
D. 200 Hz.
Correct Answer:
C. 100 Hz.
Rationale: A
full-wave bridge rectifier converts both the positive and negative half-cycles
of an AC waveform into output pulses of the same polarity. Consequently, the
rectified waveform produces two output pulses during every complete AC cycle.
The ripple frequency is therefore twice the input supply frequency. For a 50 Hz
source, \(f_{\text{ripple}}=2\times50=100\) Hz. This differs from a half-wave
rectifier, which produces one output pulse per input cycle and therefore has a
ripple frequency equal to the supply frequency. Understanding this difference
is important when designing and troubleshooting DC power supplies, particularly
when assessing smoothing capacitor performance, ripple voltage and the
operation of electronic equipment supplied by rectified AC.
Question 14. A
bipolar junction transistor operating in its active region has a measured
collector current of 4 mA and a base current of 40 µA. What is the approximate
DC current gain of the transistor?
A. 100.
B. 80.
C. 60.
D. 40.
Correct Answer:
A. 100.
Rationale: The DC
current gain of a bipolar junction transistor in the common-emitter
configuration is represented by beta, expressed as \(\beta=I_C/I_B\), where
\(I_C\) is collector current and \(I_B\) is base current. Converting the base
current into milliamperes gives 40 µA = 0.04 mA. Therefore,
\(\beta=4/0.04=100\). This means that, under the stated operating conditions,
the collector current is approximately 100 times the base current. The current
gain is not necessarily constant under all operating conditions because it can
vary with collector current, temperature and the characteristics of the
transistor. This principle is relevant to electronic switching circuits,
amplification stages and fault diagnosis involving transistor-based control
equipment.
Question 15. An
operational amplifier is connected in a non-inverting amplifier configuration.
Its feedback resistor is 90 kΩ, while the resistor connected between the
inverting input and ground is 10 kΩ. Assuming ideal operational amplifier
characteristics, what is the closed-loop voltage gain?
A. 8.
B. 9.
C. 11.
D. 10.
Correct Answer:
D. 10.
Rationale: The
voltage gain of an ideal non-inverting operational amplifier is calculated
using \(A_v=1+R_f/R_1\), where \(R_f\) is the feedback resistance and \(R_1\) is
the resistance between the inverting input and ground. Substituting the values
gives \(A_v=1+(90,000/10,000)=1+9=10\). The non-inverting configuration
produces an output signal that maintains the same phase as the input signal,
while its voltage gain is determined by the feedback resistor network. A common
source of error is using the inverting amplifier gain formula, which has a
different expression and produces a different phase relationship. Operational
amplifiers are widely used in signal conditioning, instrumentation, measurement
systems and electronic control circuits.
Question 16. In
an industrial electrical control installation, several field sensors are
connected to a programmable logic controller (PLC). What is the principal
function of the PLC input module in this arrangement?
A. To convert the
controller's processed logic into signals for external actuators.
B. To receive and condition signals from field input devices.
C. To execute the programmed instructions and determine control decisions.
D. To provide regulated electrical power to the controller's processing
circuits.
Correct Answer:
B. To receive and condition signals from field input devices.
Rationale: A PLC
input module acts as the interface between external field devices and the
programmable controller's processing system. It receives signals from devices
such as limit switches, pressure switches, proximity sensors, temperature
transmitters and other monitoring equipment. Depending on the input module
design, it may accept digital signals, analogue voltage signals or analogue
current signals and provide the necessary signal conditioning, electrical
isolation and conversion for the controller to process the information. The
PLC's central processing unit then executes the programmed logic and determines
the appropriate output response. The output module, rather than the input
module, interfaces with actuators and other controlled devices. This distinction
is important when installing, commissioning and diagnosing industrial
automation and electrical control systems.
Question 17. A
pressure transmitter uses a standard 4–20 mA output signal to represent a
measurement range of 0–100 bar. During operation, the measured output current
is 12 mA. What pressure value is being represented by the transmitter?
A. 25 bar.
B. 40 bar.
C. 50 bar.
D. 75 bar.
Correct Answer:
C. 50 bar.
Rationale: A 4–20
mA instrumentation signal uses 4 mA as the lower range value and 20 mA as the
upper range value. The difference between these values is 16 mA, representing
the full measurement span of 100 bar. At a measured current of 12 mA, the
signal is 8 mA above the lower range value. This represents \(8/16=0.5\), or
50% of the measurement span. Therefore, the pressure is \(0.5\times100=50\) bar.
The correct calculation must use the 4 mA lower reference rather than treating
zero pressure as zero current. The 4 mA starting point is commonly known as a
live zero, allowing a monitoring system to distinguish a valid zero measurement
from certain circuit faults, such as an open transmitter loop.
Question 18. A
platinum resistance temperature detector (RTD) is specified as a PT100 sensor
conforming to the IEC 60751 characteristic. What is the approximate resistance
of this sensor at 100°C?
A. 138.5 Ω.
B. 120.0 Ω.
C. 150.0 Ω.
D. 100.0 Ω.
Correct Answer:
A. 138.5 Ω.
Rationale: A
PT100 is a platinum resistance temperature detector whose nominal resistance is
100 Ω at 0°C. Its resistance increases predictably as temperature rises,
allowing temperature to be determined through electrical resistance
measurement. According to the standard IEC 60751 characteristic, the
approximate resistance at 100°C is 138.5 Ω. This relationship is commonly
expressed using the Callendar–Van Dusen equation, which accounts for the
temperature-dependent behaviour of platinum. Unlike a thermocouple, which
generates a small thermoelectric voltage due to a temperature difference, an
RTD operates by changing its resistance with temperature. PT100 sensors are
widely applied in industrial instrumentation, transformer temperature
monitoring, motor protection and process-control systems. Accurate resistance
measurement and appropriate lead-wire compensation are important when using
these sensors.
Question 19. A
three-phase induction motor is operating under normal load when one of its
supply phases becomes disconnected due to a faulty connection. The motor
continues rotating, but its operating condition becomes abnormal. Which
consequence is most likely to occur if the condition is not corrected?
A. The remaining
phase currents increase, potentially causing excessive winding heating.
B. The motor continues operating normally because the remaining phases maintain
a balanced rotating field.
C. The motor develops increased starting torque because the supply voltage is
redistributed between phases.
D. The motor's synchronous speed increases because the number of supplied
phases has decreased.
Correct Answer:
A. The remaining phase currents increase, potentially causing excessive winding
heating.
Rationale: The
loss of one supply phase in a three-phase induction motor is known as
single-phasing. When this condition occurs while the motor is already running,
the motor may continue rotating because of its existing momentum and the
remaining electromagnetic torque. However, the motor's magnetic field becomes
unbalanced, and the currents in the remaining phases can increase significantly
as the motor attempts to maintain its mechanical load. This excessive current
produces additional \(I^2R\) losses in the stator windings, resulting in
overheating and potentially severe insulation damage or complete motor failure.
The motor may also experience reduced torque, increased vibration and abnormal
noise. Appropriate phase-failure protection and overload protection are
therefore important in industrial motor installations. A technician should
investigate the supply connections, fuses, contactor contacts and protective
devices rather than allowing the motor to continue operating under this
condition.
Question 20. A
synchronous generator is designed with four magnetic poles and operates at a
frequency of 50 Hz. What is its corresponding synchronous rotational speed?
A. 750 rpm.
B. 1,000 rpm.
C. 3,000 rpm.
D. 1,500 rpm.
Correct Answer:
D. 1,500 rpm.
Rationale: The
synchronous speed of an AC generator is determined by its electrical frequency
and number of magnetic poles. The relationship is \(N_s=120f/P\), where \(N_s\)
is synchronous speed in revolutions per minute, \(f\) is frequency in hertz and
\(P\) is the total number of poles. Substituting the given values gives
\(N_s=(120\times50)/4=1,500\) rpm. This means a four-pole synchronous generator
must rotate at 1,500 rpm to produce an electrical frequency of 50 Hz. A
two-pole generator operating at the same frequency would require 3,000 rpm,
while an eight-pole generator would operate at 750 rpm. This relationship is
particularly important in power generation because generator rotational speed
and pole configuration determine the frequency of the generated electricity.
Question 21. A
three-phase induction motor has a rated mechanical output power of 7.5 kW. It
operates from a 400 V supply with a power factor of 0.8 and an efficiency of
90%. Assuming balanced operation, what is the approximate line current drawn by
the motor at its rated output?
A. 12.5 A.
B. 15.0 A.
C. 17.2 A.
D. 21.7 A.
Correct Answer:
B. 15.0 A.
Rationale: The
rated output power of an electric motor represents the mechanical power
delivered at its shaft, whereas the electrical input power is greater because
of motor losses. The input power is calculated by dividing the output power by
efficiency: \(P_{\text{in}}=7,500/0.9=8,333.33\) W. For a balanced three-phase
motor, the electrical input power is \(P_{\text{in}}=\sqrt{3}V_LI_L\cos\phi\).
Rearranging to determine line current gives
\(I_L=P_{\text{out}}/(\sqrt{3}V_L\cos\phi\eta)\). Substituting the values gives
\(I_L=7,500/(1.732\times400\times0.8\times0.9)=15.03\) A, approximately 15.0 A.
The efficiency factor must be included because the stated 7.5 kW is mechanical
output rather than electrical input. This calculation is important when
selecting motor protection, conductors and associated electrical equipment.
Question 22. An
industrial installation consumes 20 kW of active power at a lagging power
factor of 0.70. An electrical technician proposes installing a capacitor bank
to improve the power factor to 0.95 lagging without changing the active power
demand. What is the approximate reactive power rating of the capacitor bank
required?
A. 8.20 kVAr.
B. 10.50 kVAr.
C. 13.83 kVAr.
D. 18.20 kVAr.
Correct Answer:
C. 13.83 kVAr.
Rationale: Power
factor correction involves reducing the reactive power drawn from the supply by
introducing capacitive reactive power to compensate for the inductive reactive
power of the installation. The required capacitor rating is calculated using
\(Q_c=P(\tan\phi_1-\tan\phi_2)\), where \(P\) is active power, \(\phi_1\) is
the original power-factor angle and \(\phi_2\) is the corrected power-factor
angle. For the original power factor of 0.70, \(\tan\phi_1\) is approximately
1.0202, while for the improved power factor of 0.95, \(\tan\phi_2\) is
approximately 0.3287. Therefore, \(Q_c=20(1.0202-0.3287)=13.83\) kVAr. The
capacitor bank supplies approximately 13.83 kVAr of capacitive reactive power.
Proper power factor correction reduces unnecessary reactive current in the
supply network, improves voltage conditions and may reduce demand-related
electricity costs. However, capacitor bank selection must also consider
harmonics, switching arrangements and the risk of overcompensation.
Question 23. A
12.6 V battery is supplying a load drawing a current of 10 A. When the battery
is delivering this current, its measured terminal voltage falls to 12.0 V.
Assuming the battery's internal resistance remains constant, what is its
approximate internal resistance?
A. 0.012 Ω.
B. 0.040 Ω.
C. 0.100 Ω.
D. 0.060 Ω.
Correct Answer:
D. 0.060 Ω.
Rationale: When a
battery supplies current to an external load, a voltage drop occurs across its
internal resistance. The terminal voltage during discharge is given by \(V=E-Ir\),
where \(E\) represents the electromotive force, \(I\) represents the discharge
current and \(r\) represents internal resistance. Rearranging gives
\(r=(E-V)/I\). Substituting the values produces
\(r=(12.6-12.0)/10=0.6/10=0.06\) Ω. Therefore, the internal resistance is
approximately 0.060 Ω. This calculation demonstrates why the terminal voltage
of a battery under load can be lower than its open-circuit voltage. Excessive
internal resistance may indicate battery deterioration, poor internal
connections or other problems affecting its ability to deliver current. Such
measurements are useful when investigating battery performance in backup power
supplies, control systems and substation auxiliary DC systems.
Question 24. Two
protective circuit breakers are installed in series within a low-voltage
distribution system. The downstream breaker supplies a final distribution
circuit, while the upstream breaker protects the main distribution board. When
a short-circuit fault occurs on the final circuit, which arrangement best
describes the desired protection coordination between the two breakers?
A. Both breakers
should disconnect simultaneously for every fault condition.
B. The downstream breaker should clear the fault while the upstream breaker
remains closed.
C. The upstream breaker should disconnect first to isolate the entire
installation.
D. The downstream breaker should remain closed while the upstream breaker
interrupts the fault.
Correct Answer:
B. The downstream breaker should clear the fault while the upstream breaker
remains closed.
Rationale: This
arrangement is an example of selective coordination, also known as
discrimination, between protective devices. Its purpose is to ensure that the
protective device closest to a fault operates first, thereby isolating only the
affected section of the electrical installation while maintaining supply to
unaffected circuits. When a short circuit occurs downstream, the final circuit
breaker should interrupt the fault current without unnecessarily causing the
upstream main breaker to trip. Achieving this requires appropriate selection of
breaker characteristics, current ratings, time-current curves and short-circuit
performance. Depending on the devices and system design, manufacturers may also
provide tested selectivity tables to establish whether full or partial
discrimination is achieved. Poor coordination can result in unnecessary
interruption of electricity to a larger part of the installation, increasing
downtime and affecting connected equipment.
Question 25. In a
low-voltage electrical installation, the protective earthing conductor connects
exposed conductive parts of electrical equipment to the installation's earthing
system. What is the principal safety purpose of this arrangement?
A. To provide a
low-impedance fault-current path that facilitates automatic disconnection.
B. To provide the normal return path for current flowing through electrical
loads.
C. To maintain the rated operating voltage across the equipment during normal
operation.
D. To prevent excessive current from flowing through the neutral conductor
during normal operation.
Correct Answer:
A. To provide a low-impedance fault-current path that facilitates automatic
disconnection.
Rationale: Protective
earthing is intended to reduce the risk of electric shock when an insulation
failure causes a live conductor to come into contact with an exposed conductive
part of electrical equipment. The protective conductor provides a suitably
low-impedance path for the resulting fault current, allowing the associated
protective device, such as a fuse, circuit breaker or appropriate
residual-current protection arrangement, to disconnect the supply within the
required time. Without an effective protective earthing arrangement, an exposed
metal enclosure could remain at a dangerous voltage, creating a serious shock
hazard to anyone touching it. Protective earthing must not be confused with the
normal neutral-current return path because the protective conductor is not
intended to carry normal load current. Its design and installation must comply
with the applicable electrical installation requirements, including appropriate
conductor sizing, continuity and earthing arrangements. This is a fundamental
safety consideration in TANESCO-related electrical installation and maintenance
work.
Question 26. During
a routine transformer open-circuit test, the high-voltage winding is left open
while rated voltage is applied to the low-voltage winding. Which transformer
characteristic is primarily determined from this test?
A. Full-load
copper loss and percentage impedance.
B. Core (iron) loss and no-load current.
C. Full-load voltage regulation and winding temperature.
D. Short-circuit impedance and maximum fault current.
Correct Answer:
B. Core (iron) loss and no-load current.
Rationale: The
open-circuit test is conducted by applying rated voltage to one winding,
usually the low-voltage winding, while keeping the other winding open. Since
the transformer draws only a small no-load current, copper losses are
relatively small and can generally be neglected. The wattmeter reading
therefore approximates the core or iron losses, while the ammeter measures the
no-load current. The test helps assess the transformer's magnetic performance
and core condition.
Question 27. An
electrical cable has a measured resistance of 0.8 Ω at 20°C. If the conductor
is made of copper with a temperature coefficient of resistance of 0.00393 per
°C at 20°C, what will its approximate resistance be when its temperature rises
to 70°C?
A. 0.920 Ω. B.
0.957 Ω. C. 1.024 Ω. D. 1.157 Ω.
Correct Answer: B.
0.957 Ω.
Rationale: The
resistance of a metallic conductor increases as its temperature rises because
increased atomic vibration creates greater opposition to the movement of
electrical charge carriers. For a temperature range where the linear
approximation is appropriate, resistance is calculated using
\(R_t=R_{20}[1+\alpha_{20}(t-20)]\). Here, \(R_{20}=0.8\) Ω,
\(\alpha_{20}=0.00393\) per °C and the temperature increase is \(70-20=50\)°C.
Therefore, \(R_{70}=0.8[1+(0.00393\times50)]=0.8(1.1965)=0.9572\) Ω. This gives
approximately 0.957 Ω. The calculation demonstrates why conductor resistance
measured under cold conditions cannot always be used directly to assess
operating losses under normal loading. Temperature effects are important when
evaluating cable voltage drop, power losses, overheating and electrical
installation performance.
Question 28. Before
connecting two three-phase transformers in parallel, a technician performs a
polarity and phase-displacement verification. What is the main purpose of this
verification?
A. To confirm
that the transformers have identical core losses.
B. To ensure that their secondary voltages are in the correct phase
relationship.
C. To establish that both transformers have equal winding temperatures.
D. To determine the insulation resistance of their neutral conductors.
Correct Answer:
B. To ensure that their secondary voltages are in the correct phase
relationship.
Rationale: When
transformers operate in parallel, their voltage ratios, polarity, phase
sequence and phase displacement must be compatible. Incorrect polarity or phase
displacement can produce substantial circulating currents or even short-circuit
conditions when the secondary windings are connected together. Verifying the
phase relationship helps ensure safe and satisfactory parallel operation. Other
important parallel-operation requirements include compatible voltage ratios and
percentage impedances.
Question 29. An
induction motor experiences a sustained overload that causes its current to
remain above the normal operating value. Which component of a conventional
thermal-magnetic motor protection arrangement is primarily responsible for
responding to this condition?
A. The thermal
overload element, which responds to the heating effect of excessive current.
B. The magnetic instantaneous element, which responds to normal starting
current.
C. The contactor auxiliary contact, which measures motor winding temperature.
D. The circuit breaker's making mechanism, which regulates motor operating
current.
Correct Answer:
A. The thermal overload element, which responds to the heating effect of
excessive current.
Rationale: A
thermal overload element protects a motor against sustained excessive current
by responding to the heating effect produced by the overload. Depending on its
design, it may use a bimetallic element or an electronic sensing arrangement to
initiate tripping. The magnetic instantaneous element is primarily intended to
respond rapidly to high short-circuit currents rather than ordinary sustained
overloads. A contactor auxiliary contact does not directly measure winding
temperature, and a circuit breaker's making mechanism is not designed to
regulate motor current.
Question 30. A
three-phase synchronous generator operates at a constant mechanical speed and
supplies an isolated electrical load. The connected load suddenly increases
while the mechanical input power initially remains unchanged. What is the most
likely immediate effect on the generator?
A. The generated
frequency increases because the electrical demand is higher.
B. The generator automatically maintains its original frequency without any
transient change.
C. The generated frequency tends to decrease because the electrical load torque
increases.
D. The terminal voltage increases because the armature current becomes larger.
Correct Answer:
C. The generated frequency tends to decrease because the electrical load torque
increases.
Rationale: In an
isolated synchronous generator, electrical frequency is directly related to the
rotational speed of the rotor and the number of magnetic poles. When the
electrical load increases, the generator experiences a corresponding increase
in electromagnetic torque opposing the prime mover. If the mechanical input
power does not immediately increase, the rotor experiences a decelerating effect
and its speed tends to fall, resulting in a temporary reduction in generated
frequency. The governor or prime-mover control system must respond by
increasing mechanical input power to restore the rotor speed and maintain the
required frequency. Excitation control performs a different function because it
primarily regulates terminal voltage and reactive power behaviour. This
distinction is important in understanding generator load response and frequency
regulation in isolated generation systems.
📘 Get the Full Aptitude Test Questions PDF through your Gmail (Questions 1–150)
You’ve just accessed the first 30 questions. The full set of 150 expertly prepared aptitude test questions for Technician Grade II (Electrical/Electronics) – TANESCO., Is available, pay, and get access.
To get access to the full PDF, please make a payment of Tsh 10,000 to the LIPA numbers below:
After payment, please send a text message to notify us of your payment:
⚠️ Important Notice
- The PDF will be watermarked with your name and phone number and protected for personal use only.
- Redistribution, sharing, screenshotting, or copying the contents is strictly prohibited. When you share unlawfully, your name and phone number are visible and easy to trace as you leaked a document to other third parties.
- Legal action may be taken against the misuse of this material.
Thank you for supporting quality content. Best of luck in your interview preparation!